NOVEL · PRODUCTS AND SYSTEM SOLUTIONS

Det-Tronics FlexSonic Acoustic Gas Leak Detector

AC100 sensor and ATX10 transmitter for detecting ultrasound from pressurised gas leaks in outdoor and process-safety applications.

Det-Tronics FlexSonic AC100 ATX10

FlexSonic monitors the acoustic signature of pressurised leaks without waiting for a gas cloud to reach a point sensor. Its 24-band analysis and Learn function help distinguish leak noise from other ultrasonic sources.

Detection method: acoustic leak alarm. It does not identify the gas or measure ppm / %LEL concentration.

Request a Quote from NOVEL ↗

Technical Specifications

FlexSonic · AC100 / ATX10
Detection
24 discrete ultrasonic bands; non-contact pressurised-leak detection.
Output
4–20 mA + HART
Supply
24 V DC nominal; 9–30 V DC
Enclosure
316 stainless steel; IP66
Operating
−55…+75 °C
System
AC100 acoustic sensor + ATX10 transmitter
Certification
SIL 2 capable; ATEX/IECEx scope must be checked for the exact model and installation.

Coverage depends on leak pressure and rate, opening geometry, background noise and site obstructions. Reference radii in the instructions are not guaranteed coverage for every installation.

Where Is It Used?

It adds a leak-alarm layer around compressors, gas processes and outdoor industrial areas. Suitability for methane, hydrogen or another pressurised gas is assessed through leak acoustics and site conditions, rather than concentration measurement. Consider it alongside point or open-path gas detectors.

Official Manufacturer Product Page ↗